Protecting Your DC Power, Ensuring Uninterrupted Operation.
Advanced Earth Fault Location Systems for enhanced safety, reliability, and minimized downtime.
Dedicated DC Earth Fault Location System With Hooter Unit
DIGITRACE DC 361 is a dedicated monitoring equipment for floating DC systems in power station. It’s an advanced sensing system which precisely identifies the faulty feeder and complex earth faults on any floating DC system in ONLINE condition. The fault resistance range is up to 400kΩs. Online Digitrace DC 361 It is capable of finding faults in a maze of feeders with noise and other mimicking fault conditions, source of which may be perplexing and misleading. It is a Dedicated system comprising of three units : A Dedicated Transmitter unit, a dedicated receiver unit and Portable Receiver unit.
DC system grounds can result when a conduction path is formed from either the positive polarity of the system to earth ground or the negative polarity to earth ground.
Application & Functioning
- Earth Leakage Monitor is one of the most important devices used in DC power systems like battery chargers AC-DC converter system, DC-DC converter system and DCDBs.
- Taurus DIGITRACE DC 361 enables quick detection of the earth faults hence prompt corrective action can be taken.
Features
- High sensitivity
- 16 or 32 channel feeder scanning.(customizable)
- Automatic capacitance balancing
- Detects and pinpoints faults in ONLINE
- Indicates and pinpoints mixing of sources
- Digital receiver to identify and pinpoint critical earth fault in highly induced environmental conditions
- Adjustable output voltages, various DC voltage applications
- High capacity battery for long and continuous operation
- Immune to 50Hz and its harmonics
- EMC / EMI compliance
- Protected with IP 67 pelican casing
- Portable and easy to operate
Technical Specifications
Dedicated Transmitter
- Power Supply : 230 V +/- 10% AC, 50 Hz +/- 5% / built-in rechargeable battery 12 V, 7 Ah
- Digital Display : Injected voltage, DC system voltage and Injected current, Accuracy +/- 5%
- Dedicated transmitter having a number of channel / feeder is 16 as a standard and customized
- Clamp on probes as per the customer order
- Operating frequency : Very Low Frequency, less than 10 Hz
- Output voltage : Auto selected ≤ 24 V, Auto voltage injection ≤ 10% DC bus voltage
- Can be connected to any floating system from 20 VDC to 400 VDC
- Output current : ≤ 3mA
Receiver
- Power Supply : Built-in rechargeable battery 12 V backup upto 40 hrs.
- Calibrated to operating frequency of Transmitter
- Sensitivity up to 400 kΩs, upgradeable upto 1.5 MΩs
- Immune to 50 Hz and its harmonics
- Fault tracing up to 1 km (Optional 3 kms)
Atmospheric Condition
- Operating temperature : – 5 Deg C to +55 Deg C
- Storage temperature : – 10 Deg C to + 60 Deg C
- Relative Humidity : 95% non condensing
Certifications
- CPRI- IEC60068-2-27, IEC60068-2-6 IEC60068-2-78. Vibration, Shock, Bump, Damp heat & steady state test. ( CPRI Lab)
- IEC61000-4-2/2018 Electrostatic discharge immunity.IEC61000-4-8/2009 Power Frequency Magnetic Field immunity.
- IEC61000-4-3/2010 Performance test
- IEC610101 – Safety